Settings and configuration
Chapter 7
83
1SFC132003M0201
58(4) Locked rotor event of relay V7 V7 Lock Rot Yes, No No
58(5) Underload event of relay V7 V7 Underload Yes, No No
58(6) Phase imbalance event of relay V7 V7 Phase Imb Yes, No No
58(7) PTC event of relay V7 V7 PTC Yes, No No
58(8) Phase reversal event of relay V7 V7 Phase Rev Yes, No No
58(9) Overload warning event of relay V7 V7 Warn OL Yes, No No
58(10) Thyristor overload warning event of relay
V7
V7 Wa SCR OL Yes, No No
58(11) High current warning event of relay V7 V7 Wa I=High Yes, No No
58(12) Low current warning event of relay V7 V7 Wa I=Low Yes, No No
58(13) Shunt fault event of relay K7 K7 Shunt Fault Yes, No Yes
59 Fieldbus control Fieldb Ctrl Yes, No No
60 Fieldbus type Fieldb Type AS-Int, Other Other
61 Fieldbus address Fieldb Addr 0...1000 0
62 Sequence start, number of sequences No of Seq No, 2, 3 No
63 Start ramp, first sequence Start Ramp 1 1...30s, 1...120s 10s
64 Initial voltage, first sequence Init Volt 1 30...70% 30%
65 Current limit, first sequence Curr Lim 1 2.0...7.0xle 4.0xle
66 Setting current, first sequence 1st Set Ie 9.0...1207A Individual
67 Start ramp, second sequence Start Ramp 2 1...30s, 1...120s 10s
68 Initial voltage, second sequence Init Volt 2 30...70% 30%
69 Current limit, second sequence Curr Lim 2 2.0...7.0xle 4.0xle
70 Setting current, second sequence 2st Set Ie 9.0...1207A Individual
71 Start ramp, third sequence Start Ramp 3 1...30s, 1...120s 10s
72 Initial voltage, third sequence Init Volt 3 30...70% 30%
73 Current limit, third sequence Curr Lim 3 2.0...7.0xle 4.0xle
74 Setting current, third sequence 3st Set Ie 9.0...1207A Individual
75 Language Language US/UK, PL, TR, RU,
CN, DE, ES, FR, IT, NL,
PT, SE, FI
Individual
77 LCD automatic switch-off LCD Auto Off 1...255min 15min
78 Password Password 0...255 0
79 Date type Date Type ISO, CE, US ISO
80 Year Date Year 1901...2038 Individual
81 Month Date Month 1...12 Individual
82 Day Date Day 1...31 Individual
83 Hour Time Hour 0...23 Individual
84 Minutes Time Min 0...59 Individual
97 By-pass doesn’t open fault, type of opera-
tion
BP Closed Op Stop-M, Stop-A Stop-M
98 By-pass doesn’t close fault, type of opera-
tion
BP Open Op Stop-M, Stop-A Stop-M
111 Dual current limit time C Lim Y Time 0...120 s 0 s
112 Dual current limit level C Lim Y Level 2.0...7.0 x Ie 4.0 x Ie
113 Fieldbus auto disable FB Auto Dis Yes, No No
114 Start mode Start Mode Volt, Torque Volt
115 Stop mode Stop Mode Volt, Torque Volt
116 Torque limit Torque Limit 20...200% 150%
117 Tune torque control Tune T-Ctrl 30...300% 100%
123 Analog output Analog Out Yes, No No
124 Analog output, reference Anl Ref 0...10V, 0...20mA,
4...20mA
4...20mA
125 Analog output, type of value Anl Type I Amp, U Volt, P kW, P
hp, Q kVAr, S kVA, Tmp-
Mot, TmpSCR, cosPhi
I Amp
126 Analog output, current range max I Range Max 10...20000A PST(B) size
dependent
Param.
number
Description Display text Setting range Default
value
Actual
setting