Mode
: The voltage and current used for the power measurement. The setting possibilities are
shown in table 36.
Table 36: Complex power calculation
Set value
Mode
Formula used for complex power calculation
L1, L2, L3
* * *
1 1 2 2 3 3L L L L L L
S U I U I U I= × + × + ×
EQUATION1697 V1 EN-US (Equation 44)
Arone
* *
1 2 1 2 3 3L L L L L L
S U I U I= × - ×
EQUATION1698 V1 EN-US (Equation 45)
PosSeq
*
3
PosSeq PosSeq
S U I= × ×
EQUATION1699 V1 EN-US (Equation 46)
L1L2
* *
1 2 1 2
( )
L L L L
S U I I= × -
EQUATION1700 V1 EN-US (Equation 47)
L2L3
* *
2 3 2 3
( )
L L L L
S U I I= × -
EQUATION1701 V1 EN-US (Equation 48)
L3L1
* *
3 1 3 1
( )
L L L L
S U I I= × -
EQUATION1702 V1 EN-US (Equation 49)
L1
EQUATION1703 V1 EN-US (Equation 50)
L2
EQUATION1704 V1 EN-US (Equation 51)
L3
EQUATION1705 V1 EN-US (Equation 52)
The function has two stages that can be set independently.
With the parameter
OpMode1(2)
the function can be set
On
/
Off
.
The function gives trip if the power component in the direction defined by the setting
Angle1(2)
is smaller than the set pick up power value
Power1(2)
1MRK 505 370-UEN D Section 7
Current protection
Busbar protection REB670 193
Application manual