EasyManua.ls Logo

ABB REB670 Series - Page 233

ABB REB670 Series
476 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Set value for parameter
"CurrentInput”
Comment
13
MaxPh-Ph
CVGAPC function will measure ph-ph current phasor with the maximum
magnitude
14
MinPh-Ph
CVGAPC function will measure ph-ph current phasor with the minimum
magnitude
15
UnbalancePh-Ph
CVGAPC function will measure magnitude of unbalance current, which is
internally calculated as the algebraic magnitude difference between the
ph-ph current phasor with maximum magnitude and ph-ph current
phasor with minimum magnitude. Phase angle will be set to 0° all the
time
The user can select a voltage input, by a setting parameter
VoltageInput
, to measure one of
the voltage quantities shown in table 39.
Table 39: Available selection for voltage quantity within CVGAPC function
Set value for parameter
"VoltageInput"
Comment
1
phase1
CVGAPC function will measure the phase L1 voltage phasor
2
phase2
CVGAPC function will measure the phase L2 voltage phasor
3
phase3
CVGAPC function will measure the phase L3 voltage phasor
4
PosSeq
CVGAPC function will measure internally calculated positive sequence
voltage phasor
5
-NegSeq
CVGAPC function will measure internally calculated negative sequence
voltage phasor. This voltage phasor will be intentionally rotated for 180°
in order to enable easier settings for the directional feature when used.
6
-3*ZeroSeq
CVGAPC function will measure internally calculated zero sequence voltage
phasor multiplied by factor 3. This voltage phasor will be intentionally
rotated for 180° in order to enable easier settings for the directional
feature when used.
7
MaxPh
CVGAPC function will measure voltage phasor of the phase with
maximum magnitude
8
MinPh
CVGAPC function will measure voltage phasor of the phase with
minimum magnitude
9
UnbalancePh
CVGAPC function will measure magnitude of unbalance voltage, which is
internally calculated as the algebraic magnitude difference between the
voltage phasor of the phase with maximum magnitude and voltage
phasor of the phase with minimum magnitude. Phase angle will be set to
0° all the time
10
phase1
-
phase2
CVGAPC function will measure the voltage phasor internally calculated as
the vector difference between the phase L1 voltage phasor and phase L2
voltage phasor (UL1-UL2)
11
phase2
-
phase3
CVGAPC function will measure the voltage phasor internally calculated as
the vector difference between the phase L2 voltage phasor and phase L3
voltage phasor (UL2-UL3)
12
phase3
-
phase1
CVGAPC function will measure the voltage phasor internally calculated as
the vector difference between the phase L3 voltage phasor and phase L1
voltage phasor (UL3-UL1)
13
MaxPh-Ph
CVGAPC function will measure ph-ph voltage phasor with the maximum
magnitude
14
MinPh-Ph
CVGAPC function will measure ph-ph voltage phasor with the minimum
magnitude
15
UnbalancePh-Ph
CVGAPC function will measure magnitude of unbalance voltage, which is
internally calculated as the algebraic magnitude difference between the
ph-ph voltage phasor with maximum magnitude and ph-ph voltage
phasor with minimum magnitude. Phase angle will be set to 0° all the
time
1MRK 505 370-UEN D Section 10
Multipurpose protection
Busbar protection REB670 227
Application manual

Table of Contents

Related product manuals