220kV Busbar
300/1
15 / 0,1kV
4000/5
100 MVA
242/15,65 kV
Yd5
U
L1L2
, U
L2L3
G
P Q
100MVA
15,65kV
IEC09000041-1-en.vsd
IED
IEC09000041-1-EN V1 EN-US
Figure 198: Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure 198, it is necessary to
do the following:
1. Set correctly all CT and VT data and phase angle reference channel
PhaseAngleRef
using
PCM600 for analog input channels
2. Connect, in PCM600, measurement function to the generator CT & VT inputs
3. Set the setting parameters for relevant Measurement function as shown in the following
table:
Section 14 1MRK 505 370-UEN D
Monitoring
362 Busbar protection REB670
Application manual