EasyManua.ls Logo

ABB REB670 Series - Page 446

ABB REB670 Series
476 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IEC07000198-2-en.vsd
SMAI1:1
BLOCK
DFTSPFC
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI1:13
BLOCK
DFTSPFC
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI1:25
BLOCK
DFTSPFC
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
IEC07000198 V3 EN-US
Figure 231: Configuration for using an instance in task time group 1 as DFT reference
Assume instance SMAI7:7 in task time group 1 has been selected in the configuration to control
the frequency tracking . Observe that the selected reference instance (i.e. frequency tracking
master) must be a voltage type. Observe that positive sequence voltage is used for the
frequency tracking feature.
For task time group 1 this gives the following settings (see Figure
230 for numbering):
SMAI1:1:
DFTRefExtOut
=
DFTRefGrp7
to route SMAI7:7 reference to the SPFCOUT output,
DFTReference
=
DFTRefGrp7
for SMAI1:1 to use SMAI7:7 as reference (see Figure 231) SMAI2:2 –
SMAI12:12:
DFTReference
=
DFTRefGrp7
for SMAI2:2 – SMAI12:12 to use SMAI7:7 as reference.
For task time group 2 this gives the following settings:
SMAI1:13 – SMAI12:24:
DFTReference
=
ExternalDFTRef
to use DFTSPFC input of SMAI1:13 as
reference (SMAI7:7)
For task time group 3 this gives the following settings:
SMAI1:25 – SMAI12:36:
DFTReference
=
ExternalDFTRef
to use DFTSPFC input as reference
(SMAI7:7)
Example 2
Section 20 1MRK 505 370-UEN D
Basic IED functions
440 Busbar protection REB670
Application manual

Table of Contents

Related product manuals