EasyManua.ls Logo

ABB REC 561 - Setting Table

ABB REC 561
643 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB Network Partner AB
I/O system configuration
Version 1.0-00
1MRK 580 190-XEN
Page 4 - 24
6.2 Setting table
Table 3: Setting table for binary input module (BIM), binary output
module (BOM), and input/output module (IOM)
PARAMETER: SETTING RANGE: DESCRIPTION:
IOxx-BINAMEy 13 characters Name of binary input No. y,
used for BIM and IOM. To be
set from CAP 531. For REL 531
it is also settable from SMS or
built-in MMI.
IOxx-BONAMEy 13 characters Name of binary output No. y,
used for BOM and IOM. To be
set from CAP 531. For REL 531
it is also settable from SMS or
built-in MMI.
OscBlock 1-40 Hz Oscillation blocking frequency,
common for all channels on I/O
module BIM. To be set from
SMS or built-in MMI.
OscRel 1-40 Hz Oscillation release frequency,
common for all channels on I/O
module BIM. To be set from
SMS or built-in MMI.
Operation On, Off I/O module in operation. Opera-
tion Off puts the I/O module in a
non-active state. To be set from
SMS or built-in MMI.

Table of Contents

Related product manuals