ABB REC 561 - Settings During Test; Test Mode; Activation of Manual Triggering

ABB REC 561
643 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Disturbance report - Settings
ABB Network Partner AB
1MRK 580 133-XEN
Page 7 - 61
Version 1.0-00
3 Settings during test
3.1 Test mode During testing, the operation of the Disturbance Report is required. The
setting of this operation is found at the MMI submenu:
Test
Test Mode
DisturbReport
Operation, DisturbSummary
When TestMode is set to On (Test/Mode/Operation = On), the setting of
the Disturbance Report parameters have the following impact:
Operation = Off DisturbSummary = Off
Disturbances are not stored.
LED information is not shown on the MMI and not stored.
No Disturbance Summary is scrolled on the MMI.
Operation = Off DisturbSummary = On
Disturbances are not stored.
LED information (yellow - start, red - trip) are shown on the built-in
MMI, but not stored in the terminal.
Disturbance summary is automatically scrolled on the built-in MMI
for the two latest registered disturbances, until cleared. The informa-
tion is not stored in the terminal.
Operation = On DisturbSummary = Off or On
The Disturbance Report works as in normal mode.
Disturbances are stored. Data can be read from the built-in MMI, a
front-connected PC, or SMS.
LED information (yellow - start, red - trip) is stored.
Disturbance Summary is automatically scrolled on the built-in MMI
for the two latest registered disturbances, until cleared.
All disturbance data stored during test mode remains in the terminal
when returning to normal mode.
3.2 Activation of manual
triggering
A Disturbance Report can be manually triggered from the built-in MMI, a
front-connected PC, or SMS. When the trig is activated, the manual trig
signal is generated. This feature is especially useful for testing.