EasyManua.ls Logo

ABB REC 561 - Tripping Logic Circuits

ABB REC 561
643 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Tripping logic
ABB Network Partner AB
1MRK 580 120-XEN
Page 5 - 3
Version 1.0-00
Signal To phase...
L1TRIP L1
L2TRIP L2
L3TRIP L3
External tripping signals can also cause a single-phase tripping without
any restriction.
Fig. 2 Single-phase front logic—simplified logic diagram
You can configure the TRIP-TRSPE signal to the output signal of the EF-
--TREF overcurrent, earth-fault, protection function (directional and non-
directional). This enables single-phase tripping when the faulty phase is
detected by some other phase-selection element such as the phase selec-
tion in distance protection.
2.3 Tripping logic circuits Fig. 3 shows a simplified illustration of the tripping logic circuits. The
TRIP-BLOCK signal might block the operation of the complete tripping
unit. In a similar way, an external TRIP-EXTTRIP signal can cause
instantaneous three-phase tripping if the function has not been blocked by
external signal or the terminal has been switched to operational testing
mode with activated blocking. A functional TRIP-PTPTRIP input signal
prepares the three-phase tripping conditions for any of the tripping signals
arriving from the front logics. Timers, delayed for 2 seconds at drop-out,
assure correct three-phase tripping for evolving faults.
TRIP-TRTP
TRIP-EXTL1
TRIP-PSL1
TRIP-EXTL2
TRIP-PSL2
1
V
1
V
1
V
L1TRIP
L2TRIP
L3TRIP
To
Fig 3
TRIP-EXTL3
TRIP-PSL3
TRIP-TRSPE
TRIP-TRSPZ
t
50ms
Loop delay
&
&
1
V
&
&
&
&
Loop delay
1
V
&
1
V
1
V
1
V
1
V
(X80120-2)

Table of Contents

Related product manuals