6 Appendix
6.1 Terminal diagram
Fig. 2 Simplified terminal diagram of the Pulse Counter function
6.2 Signal list
PulseCounter
BLOCK
TMIT_VAL
BIM_CONN
NAME
INVALID
RESTART
BLOCKED
NEW_VAL
(X80187-2)
PCxx
Table 1: Input and output signals for Pulse Counter No. xx
IN: DESCRIPTION:
PCxx-BLOCK Input to block the counter
PCxx-TMIT_VAL Pulse input to perform an additional reading
of the counter value. The reading is per-
formed on the positive flank of the pulse
PCxx-BIM_CONN Input to be connected to the used input of
the function block for the Binary input mod-
ule (BIM)
OUT: DESCRIPTION:
PCxx-INVALID The output is set if the Binary input module
(BIM), where the pulse input is located, fails
or has wrong configuration
PCxx-RESTART The output is set when the reported value
does not comprise a complete integration
cycle.
PCxx-BLOCKED The output is set when the BLOCK input is
set or the Binary input module (BIM), where
the pulse input is located, is inoperative.
PCxx-NEW_VAL The output is set if the counter value was
updated since the last report (pulse output)