ABB Network Partner AB
Configurable logic
Version 1.0-00
1MRK 580 161-XEN
Page 4 - 32
5Testing
You can separately test configuration logic circuits for each group and
each circuit. For each block, you must configure all:
Input signals to the corresponding binary inputs.
Output signals to the corresponding binary outputs of the terminal.
Then check the operation of each separate block by applying the rated
DC voltage to the corresponding binary inputs and observing the logic
statuses of the corresponding binary outputs.
Configuration from the built-in MMI of the corresponding logic circuits
for the binary inputs for REL 531 occurs under:
Configuration
FunctionInputs
AND (OR, Timer, Pulse, INV, SR)
Slotxx-IOMy (BIMy)
and for the binary outputs under:
Configuration
Slotxx-IOMy (BOMy)
AND (OR, Timer, Pulse, INV, SR)
The configuration logic blocks included in the operation of the different
functions must be tested at the same time as their corresponding functions.