ABB Network Partner AB
Apparatus control
Version 1.0-00
1MRK 580 150-XEN
Page 6 - 40
4.2.5 Local panel (back-up
panel)
The connection of an external local panel to the apparatus control mod-
ules is done via binary inputs. Fig. 25 shows one example of a solution.
This solution of local control considers the interlocking function. The
panel can also be used as an back-up panel, but the outputs from the panel
are then connected directly to the high-voltage apparatuses. The position
indications are normally directly connected to the panel to get independ-
ent information about the apparatus positions. At use as back-up panel,
the select and execute inputs into the control terminal must be blocked, for
example, with AND gates with the condition no back-up.
Fig. 25 Connection of an external local panel via binary input board
to apparatus control modules
BAYCON
S_R
S_S
L_L
LOCAL
Station/Remote
Local
COMCON
Apparatus 1
L_SEL_O
L_SEL_C
L_OPEN
L_CLOSE
LOCAL
Local panel
To other
apparatus
in the bay
Input
board
From station MMI
Selection app. 1
Common open
Common close
(X80150-25)