ABB Network Partner AB
Apparatus control
Version 1.0-00
1MRK 580 150-XEN
Page 6 - 4
Block/deblock operation (per apparatus or bay)
Override of reservation, interlocking and/or synchro-check
Selection of operator place, station and/or remote
Block/deblock updating of the position indications (per apparatus or
bay)
Setting of the position indication, open/close
Local
These commands are supported from the local MMI (back-up panel):
Select, open/close
Execute, open/close
Override, reservation and/or interlocking
Set operator place to local (switch on the back-up panel)
Automatic functions
An automatic program (placed in REC 561 or in external equipment) can
be connected to the apparatus control. These signals can be connected to
the apparatus control:
Signals for select (open/close)
Signals for execute (open/close)
Cancel the selection
Signal to reserve the apparatus for automatic functions. Used when
the apparatus is included in a sequence
2.3 Selection and
reservation
The purpose of the reservation and selection is to prevent double opera-
tion, either in the bay itself or in the complete station. For an operation in
the bay, the reservation part always reserves the own bay. The engineer
can include or exclude the part that reserves other bays.
The selection and reservation function consists of four parts:
1. Reservation of the own bay
2. Requesting reservation of other bays and handling of the acknowledge-
ment signals
3. Replying to reservation requests
4. Permitting selection of apparatuses, depending on reservations
The selection and reservation function has two ways of starting. It starts
when a request select signal is set in the own bay or when it receives a
request for reservation from another bay.