EasyManua.ls Logo

ABB REC 561 - Setting Table

ABB REC 561
643 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB Network Partner AB
Tripping logic
Version 1.0-00
1MRK 580 120-XEN
Page 5 - 8
4.3 Setting table
TRIP-PSL3 Necessary condition for single phase trip in phase L3. Generally connected to protective
functions with phase selective operation
TRIP-PTPTRIP Turns the tripping logic into three phase operating mode.
TRIP-TRSPZ Initiation of single phase tripping. Requires a phase selection signal. In opposite case initi-
ate 50 ms delayed three phase tripping.
TRIP-TRTP Initiation of three phase tripping.
OUT: DESCRIPTION:
TRIP-GTRIP General information on tripping caused by tripping logic within the terminal.
TRIP-SPTRIP General information on single phase tripping caused by tripping logic within the terminal
TRIP-TPTRIP General information on three phase tripping caused by tripping logic within the terminal
TRIP-TRIPL1 Trip in phase L1
TRIP-TRIPL2 Trip in phase L2
TRIP-TRIPL3 Trip in phase L3
IN: DESCRIPTION:
PARAMETER: SETTING RANGE: DESCRIPTION
Operation Off, 3ph, 1ph Operating mode of the tripping logic.
Off: the operation is disabled.
3ph: only three phase tripping is possible.
1ph: single phase or three phase tripping, dependent on combina-
tion of different input signals

Table of Contents

Related product manuals