Function:
1 Settings, introduction
The main part of the settings for the Disturbance Report is found on the
built-in, man-machine interface (MMI) at:
Settings
DisturbReport
The settings include:
Operation Disturbance Report (On/Off)
RecordingTimes Recording times for the Disturbance Recorder and
the event/indication logging, including pre-fault
time, post-fault time, and limit time for the entire
disturbance
BinarySignals Selection of binary signals, trig conditions and
MMI indication mask
AnalogSignals Recording mask and trig conditions
FaultLocator Filter time and distance measurement unit (km/
miles/%)
User-defined names of analogue signals can be set at:
Configuration
AnalogInputs
The user-defined names of binary signals can be set at:
Configuration
DisturbReport
Input n (1-48)
The analogue and binary signals appear with their user-defined names.
An additional setting is found at:
Service Report
DisturbReport
This parameter can be read and set:
SequenceNo Sequence number (0-255) (normally not necessary
to set)