Disturbance report - Settings
Version 1.0-00
1MRK 580 133-XEN
Page 7 - 58
1.1 Settings during normal
conditions
2 Operation
MMI submenu:
Settings
DisturbReport
Operation
Operation can be set to On or Off. If Off is selected, note that no Distur-
bance Report is registered, including Indications, Fault locator, Event
Recorder, and Disturbance Recorder.
Operation = Off:
Disturbances are not stored.
LED information (yellow - start, red - trip) is not stored or changed.
No Disturbance Summary is scrolled on the built-in MMI.
Operation = On:
Disturbances are stored, disturbance data can be read from the built-
in MMI and from a front-connected PC or Station Monitoring Sys-
tem (SMS).
LED information (yellow - start, red - trip) is stored.
The Disturbance Summary is automatically scrolled on the built-in
MMI for the two latest registered disturbances, until cleared.
Table 1: How the settings affect different functions in the Disturbance Report
MMI
Setting
menu
Function Disturbance
Summary
(scrolled on
MMI)
Disturbance
Recorder
Indications Event list
(SMS)
Trip
values
Fault
locator
Operation Operation (On/Off) Yes Yes Yes Yes Yes Yes
Recording
times
Recording times
(tPre, tPost, tLim)
No Yes No Yes No No
Binary sig-
nals
Trig operation and
trig level
Yes Yes Yes Yes Yes Yes
Indication mask (for
automatic scrolling)
Yes No No No No No
Analogue
signals
Operation (On/Off) No Yes No No No No
Trig over/under
function
Yes Yes Yes Yes Yes Yes
Fault Loca-
tor
Fault locator set-
tings (tFilter, Dis-
tance Unit)
No No No No No Yes