Function:
1 Application
1.1 Synchronism check The synchro-check function is used for controlled closing of a circuit in an
interconnected network. When used, the function gives an enable signal at
satisfied voltage conditions across the breaker to be closed. When there is a
parallel circuit established, the frequency is normally the same at the two
sides of the open breaker. At power swings, e.g. after a line fault, an oscillat-
ing difference can appear. Across the open breaker, there can be a phase
angle and a voltage amplitude difference due to voltage drop across the par-
allel circuit or circuits. The synchro-check function measures the difference
between the U-line and the U-bus, regarding voltage (UDiff), phase angle
(PhaseDiff), and frequency (FreqDiff). It operates and permits closing of the
circuit breaker when these conditions are simultaneously fulfilled.
The voltages U-line and U-bus are higher than the set value for
UHigh of the rated voltage U
r
/sqr3.
The differences in the voltage and phase angles are smaller than the
set values of UDiff and PhaseDiff.
The difference in frequency is less than the set value of FreqDiff.
The bus frequency must also be within a range of ±5 Hz from the
rated frequency.
The function can be used as a condition to be fulfilled before the breaker
is closed at manual closing and/or together with the auto-recloser func-
tion.
Fig. 1 Synchronism check
The voltage circuits are arranged differently depending on the number of
synchro-check functions that are included in the control terminal.
SYN 1
UHigh>70-100% Ur
UDiff<5-50% Ur
PhaseDiff<5-75
o
FreqDiff<50-300mHz
Fuse fail
Fuse fail
U-Line
Line
reference
voltage
(X80167-1)
U-Line
U-Bus
5
Synchronism and energizing
check for double circuit breakers
and voltage selection
1MRK 580 167-XEN