EasyManua.ls Logo

ABB REC 561 - Recommendations for Output Signals

ABB REC 561
643 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Auto-reclosing - Single- and/or
three-phase
ABB Network Partner AB
1MRK 580 170-XEN
Page 5 - 67
Version 1.0-00
AR01-TRSOTF
is connected to the internal line protection, distance protection, trip
switch-onto-fault.
AR01-TPTRIP
is connected to the internal function TRIP, or to a binary input. The protec-
tion functions that give a three-phase trip are supposed to be routed via that
function.
3.2 Recommendations for
output signals
AR01-READY
can be connected to the Zone extension of a line protection. It can also be
used for indication, if required.
AR01-SP1
single-phase reclosing in progress is used to temporarily block an Earth-
fault protection and/or a Pole disagreement function during the single-
phase open interval.
AR01-CLOSECB
connect to a binary output relay for breaker closing command.
AR01-P3PH
prepare three-phase trip: Connect to TRIP-PTPTRIP.
AR01-P1PH
permit single-phase trip: Can be connected to a binary output for connec-
tion to external protection or trip relays. In case of total loss of auxiliary
voltage, the output relay drops, and does not allow single-phase tripping.
If needed to invert the signal, it can be made by a break contact of the out-
put relay.
The other output signals can be connected for indication, disturbance
recording, and so on, as required.

Table of Contents

Related product manuals