Apparatus control
ABB Network Partner AB
1MRK 580 150-XEN
Page 6 - 41
Version 1.0-00
4.2.6 Built-in MMI The high-voltage apparatus can be operated from the built-in MMI via the
SingleCmdFunc block. The SingleCmdFunc block, which must be acces-
sible from the built-in MMI, can be defined from the SMS. The naming of
the signals in the SingleCmdFunc block can be defined from the SMS and
the CAP 531 configuration tool. Fig. 26 shows an example how to con-
nect a SingleCmdFunc block to the apparatus control modules. The com-
mand dialogue from the built-in MMI is performed in two steps, see
“Command function” 1MRK 580 165-XEN.
Fig. 26 Connections between a SingleCmdFunc-block controlled from
the built-in MMI and the apparatus control modules
4.2.7 Interlocking Fig. 27 shows the connection between an interlocking module and appara-
tus control modules. The input is activated when the apparatus is inter-
locked. The interlocking information within the REC 561 control terminal
are taken from the binary input boards. Information from other bays are
transferred over the station bus. The “Reservation function” on page 26
describes the method for transferring these data.
Fig. 27 Connection of an interlocking module to apparatus control
modules
COMCON
Apparatus 1
L_SEL_O
L_SEL_C
L_OPEN
L_CLOSE
LOCAL
SingleCmdFunc
OUT1
OUT2
OUT3
OUT4
OUT16
Pulse
INPUT OUT
.
.
≥1
Pulse
INPUT OUT
Pulse length = 1 s
Apparatus 1 open
Apparatus 1 close
Defined as pulse outputs
LOCAL
From BAYCON
≥1
(X80150-26)
COMCON
OVERRIDE
Interlocking
ITL
&
Interlocked
SWICON
INT_LOCK
.
.
.
Signals from
binary input
boards and
from other
bays
(X80150-27)