Breaker-failure protection
Version 1.0-00
1MRK 580 171-XEN
Page 5 - 84
The application functions of the protection are:
Individual phase-current detection
Two time steps, one for retrip of the related circuit breaker and one
for the back-up trip of the adjacent circuit breakers
Selection of current controlled or unconditional retrip
Phase separated timers correct timing at an evolving fault
Accurate timers and current elements reset in 10 ms, allowing the
use of short back-up trip time
Fig. 2 Time sequence
(X80171-2)
40ms
20ms
<10ms
40ms
20ms
<10ms
30ms
Relay
time
Start BFP
Normal
CB opening
CB opening time
Marginal
BFP
time
CB opening time
Marginal
BFP
time
110ms
Retrip
original CB
150ms
General trip
adjacent CB