Apparatus control
ABB Network Partner AB
1MRK 580 150-XEN
Page 6 - 27
Version 1.0-00
3. After acknowledgement from all bays, the select output (SELx) from
BAYCON activates the SELECT in COMCON and allows the execute
command to pass through.
4. When SELECT in SWICON is activated, SWICON with the signals
OPEN/CLOSE/EXECUTE from COMCON gives an execution signal
(open/close) using the output signals SEL_OPEN/CLOS and
EXE_OPEN/CLOS.
5. The signal SEL_RES is resetting the selection request (RQ_SEL) after
successful operation (that is, new position reached) or command error.
SEL_RES is active until SELECT is reset.
.
Fig. 14 The reservation function within the own bay
BAYCON
RQ_SEL1
RQ_SEL2
SEL1
SEL2
COMCON
SEL_RES
SELECT
RQ_SEL
S_SEL_O
SWICON
SELECT
SEL_RES
From MMI
1
2
3
4
5
COMCON
SEL_RES
SELECT
RQ_SEL
S_SEL_O
SWICON
SELECT
SEL_RES
From MMI
ACK_F_B
RE_BAYS
Acknowledgement from other bays
Reserve
other
bays
ANY_ACK
Reset
(X80150-14)