Construction and hardware
characteristics - REC 561
ABB Network Partner AB
1MRK 580 148-XEN
Page 2 - 29
Version 1.0-00
Man machine interface (MMI) is built-in to the front cover and con-
tains LEDs, an LCD and an optical connector for a front-connected
PC. For this front communication, you need an optional special
cable, with an opto-to-RS232, built-in converter.
Optionally these hardware modules are available:
Transformer module with five voltage and five current input trans-
formers (position S2).
A/D-conversion (AD) module for up to 10 analogue inputs, operat-
ing with a sampling frequency of 2000 Hz. It has a bandwidth of
250 Hz, and a dynamic range for currents, from 0,01 to 100 I
r
, and
for voltages, from 0,01 to 2 U
r
, (position S8).
Up to 11 additional input/output modules, that can be of type Binary
input module (16 inputs), Binary output module (24 relays or 12
command relays), a combined Binary input/output module (8 inputs
and 12 output relays) and a mA input module for transducer inputs.
(all modules in positions S16 to S36).
One additional optical serial communication module, intended for
remote fibre optic SPA communication. Having two modules will
enable the terminal to be a part of SMS in parallel with a Substation
Automation System (SA). The module is placed in a slot at the rear
of the Main processing module.
Fig. 2 Basic block diagrams
(X80148-2)
I
U
A/D
SP 1
SP 2
SP 3
SP 4
SP 5
SP 6
SP 7
SP 8
SP 9
SP 10
32 bit microcontroler
Communication
in
out
in
out
MMI unit
MMI PC/SMS
SCS

Table of Contents