ABB Network Partner AB
Interlocking
Version 1.0-00
1MRK 580 151-XEN
Page 6 - 190
IFxx-Q7EX3 Input for an external condition for apparatus
Q7
IFxx-Q7EX4 Input for an external condition for apparatus
Q7
Table 2: Output signals for ABC_LINE
OUT: DESCRIPTION:
IFxx-Q0CLREL Closing of Q0 is allowed
IFxx-Q0CLITL Closing of Q0 is forbidden
IFxx-Q9REL Switching of Q9 is allowed
IFxx-Q9ITL Switching of Q9 is forbidden
IFxx-Q1REL Switching of Q1 is allowed
IFxx-Q1ITL Switching of Q1 is forbidden
IFxx-Q2REL Switching of Q2 is allowed
IFxx-Q2ITL Switching of Q2 is forbidden
IFxx-Q7REL Switching of Q7 is allowed
IFxx-Q7ITL Switching of Q7 is forbidden
IFxx-Q51REL Switching of Q51 is allowed
IFxx-Q51ITL Switching of Q51 is forbidden
IFxx-Q52REL Switching of Q52 is allowed
IFxx-Q52ITL Switching of Q52 is forbidden
IFxx-Q8REL Switching of Q8 is allowed
IFxx-Q8ITL Switching of Q8 is forbidden
IFxx-Q1OPTR Signal is 1 if Q1 is open
IFxx-Q1CLTR Signal is 1 if Q1 is closed
IFxx-Q2OPTR Signal is 1 if Q2 is open
IFxx-Q2CLTR Signal is 1 if Q2 is closed
IFxx-Q7OPTR Signal is 1 if Q7 is open
IFxx-Q7CLTR Signal is 1 if Q7 is closed
IFxx-Q1Q2OPTR Signal is 1 if Q1 or Q2 or both are open
IFxx-Q1Q2CLTR Signal is 1 if Q1 and Q2 are closed
IFxx-VPQ1TR Switch status of Q1 is valid (open or closed)
IFxx-VPQ2TR Switch status of Q2 is valid (open or closed)
IFxx-VPQ7TR Switch status of Q7 is valid (open or closed)
IFxx-VPQ1Q2TR Switch status of Q1 and Q2 are valid (open
or closed)
Table 1: Input signals for ABC_LINE
IN: DESCRIPTION: