Command function
ABB Network Partner AB
1MRK 580 165-XEN
Page 6 - 215
Version 1.0-00
4 Commands
The outputs of the Single Command function block can be activated from
the built-in MMI. This can be performed under the menu:
Command
CDxx (xx=01 for REL 531, xx=01-11 for REC 561)
Fig. 4 shows the dialogue box for the built-in MMI after the selection of
the command menu above. The display shows the name of the output to
control (CmdOut1) and the present status (Old) and proposes a new value
(New).
Fig. 4 Command dialogue to control an output from the Single Com-
mand function block
The dialogue to operate an output from the Single Command function
block is performed from different states as follows:
1. Selection active; select the:
C button, and then the No box activates.
Up arrow, and then New: 0 changes to New: 1. The up arrow
changes to the down arrow.
E button, and then the Yes box activates.
2. Yes box active; select the:
C button to cancel the action and return to the CMD/CDxx menu
window.
E button to confirm the action and return to the CMD/CDxx menu
window.
Right arrow to activate the No box.
E
C
Ready Start Trip
RE. 5.. VER 1.0
C = Clear LEDs
E = Enter menu
green yellow red
LEDs
optical connector
for local PC
liquid crystal display
four rows
16 characters/row
push buttons
(X80165-4)