ABB Network Partner AB
Measurement of alternating
quantities
Version 1.0-00
1MRK 580 159-XEN
Page 7 - 28
HiWarn (0-99999)A Determines the operating value of the monitoring element which pro-
duces logical signal DA0n-HIWARN (n=6..10)
HiAlarm (0-99999)A Determines the operating value of the monitoring element which pro-
duces logical signal DA0n-HIALARM (n=6..10)
EnDeadB Off, On Enables (On) or disables (Off) the amplitude dead-band supervision
function
DeadBand (0-99999)A Width of the amplitude dead-band within the ADBS function
EnIDeadB Off, On Enables (On) or disables (Off) the integrating dead-band supervision
function.
IDeadB (0-99999)A Determines the width of the band within the IDBS function. Be aware of
the sampling frequency
EnDeadBP Off, On Enables (On) or disables (Off) the periodic dead-band reporting
Mean voltage measuring channel
Operation Off, On Operation of the measuring channel enabled (On) or disabled (Off)
RepInt (0-3600)Seconds Duration of time interval between two reports at periodic reporting
function. Setting to 0 disables the periodic reporting.
EnAlarms Off, On Produces an immediate event at operation of any alarm monitoring ele-
ment, when On
EnAlRem Off, On Produces an immediate event at reset of any alarm monitoring element,
when On.
Hysteres (0.0-1999.9)kV Hysteresis for the set values of the monitoring elements in one measur-
ing channel.
LowAlarm (0.0-1999.9)kV Determines the operating value of the monitoring element which pro-
duces logical signal DA11-LOWALARM
LowWarn (0.0-1999.9)kV Determines the operating value of the monitoring element which pro-
duces logical signal DA11-LOWARN
HiWarn (0.0-1999.9)kV Determines the operating value of the monitoring element which pro-
duces logical signal DA11-HIWARN
HiAlarm (0.0-1999.9)kV Determines the operating value of the monitoring element which pro-
duces logical signal DA11-HIALARM
EnDeadB Off, On Enables (On) or disables (Off) the amplitude dead-band supervision
function
DeadBand (0.0-1999.9)kV Width of the amplitude dead-band within the ADBS function
EnIDeadB Off, On Enables (On) or disables (Off) the integrating dead-band supervision
function.
IDeadB (0.0-1999.9)kV Determines the width of the band within the IDBS function. Be aware of
the sampling frequency
EnDeadBP Off, On Enables (On) or disables (Off) the periodic dead-band reporting