ABB Network Partner AB
Disturbance report - Settings
Version 1.0-00
1MRK 580 133-XEN
Page 7 - 64
IndicationMask Masked, Show Masked=the signal is not automatically
scrolled,
Show=the signal is automatically scrolled on
the MMI in the Disturbance summary
Analog/U1 - U5:
Operation Off, On On=the signal is recorded in the Distur-
bance recorder
Off=the signal is not recorded
Trig U> Off, On Over trig operation
U> (0 - 200)% of Ur/sqr3 Over trig value
Trig U< Off, On Under trig operation
U< ( 0 - 110)% of Ur/sqr3 Under trig value
Analog/I1 - I5:
Operation Off, On On=the signal is recorded in the Distur-
bance recorder
Trig I> Off, On Over trig operation
I> (0 - 5000)% of Ir Over trig value
Trig I< Off, On Under trig operation
I< (0 - 200)% of Ir Under trig value
ServiceReport/DisturbReport/SequenceNo:
SequenceNo (0-255) Sequence no. of the disturbance
PARAMETER: SETTING RANGE: DESCRIPTION: