ABB Network Partner AB
Default configuration REC 561
Version 1.0-00
1MRK 580 188-XEN
Page 9 - 2
2 Application
The default configuration consists of type solutions for a double busbar
and single, circuit-breaker arrangement that includes three disconnectors
and one earthing switch. Use the copy/past and find/replace commands in
CAP 531 to extend the number of apparatuses and bays (option). Connec-
tions of optional functions are not in the default configuration, but can be
found under the functions respectively in the User’s Guide for REC 561
or when the function is connected to the apparatus control function in
Apparatus Control (1MRK 580 150-XEN).
The configuration is divided into several worksheets, which are com-
mented below.
2.1 General For this default configuration, the function selector in the CAP 531 has
these settings:
The settings in table 1 mean:
The apparatus control function is activated.
No bays in the terminal have more than 8 apparatuses.
No external selection relays are used.
External synchro-check is used.
The binary input module of type BIM is defined as I/O module 1.
Table 1: Selected functions in the default configuration
Function group Selector Value
AppControlType APCACTIVE 1=ON
AppControlType APCGT8BAYS 0=0 bay > 8 app
AppControlType APCSELSUP 0=None
AppControlType APCSYNC 1=External/None Synchrocheck
I/O-module01 Type_IO1 1=BIM
I/O-module02 Type_IO2 2=BOM
I/O-module03 Type_IO3 0=None
I/O-module04 Type_IO4 0=None
I/O-module05 Type_IO5 0=None
I/O-module06 Type_IO6 0=None
I/O-module07 Type_IO7 0=None
I/O-module08 Type_IO8 0=None
I/O-module09 Type_IO9 0=None
I/O-module10 Type_IO10 0=None
I/O-module11 Type_IO11 0=None
I/O-module12 Type_IO12 0=None
I/O-module13 Type_IO13 0=None
InterlockType ILTYPE1 2=ABC_LINE