EasyManua.ls Logo

ABB RED650 - Page 184

ABB RED650
454 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
step1 0I 1.2 3I³ ×
EQUATION1201 V3 EN-US (Equation 115)
The current setting for step 1 is chosen as the largest of the above calculated
residual currents, measured by the protection.
Step 2
M15282-144 v7
This step has directional function and a short time delay, often about 0.4 s. Step 2
shall securely detect all earth faults on the line, not detected by step 1.
IN
>
One- or two-phase earth-fault
3I
0
IEC05000154-en-2.vsd
IEC05000154 V2 EN-US
Figure 88: Step 2, check of reach calculation
The residual current, out on the line, is calculated at an operational case with
minimal earth-fault current. The requirement that the whole line shall be covered
by step 2 can be formulated according to equation 116.
step2 0
I 0.7 3I (at remote busbar)³ ×
EQUATION1202 V4 EN-US (Equation 116)
To assure selectivity the current setting must be chosen so that step 2 does not
operate at step 2 for faults on the next line from the remote substation. Consider a
fault as shown in Figure
89.
Section 8 1MRK 505 393-UEN B
Current protection
178 Line differential protection RED650 2.2 IEC
Application manual

Table of Contents

Other manuals for ABB RED650

Related product manuals