Section 7 Troubleshooting
7.1 Fault tracing
7.1.1 Identifying hardware errors
1. Check the module with an error.
Check the IED supervision events in Main menu/Monitoring/IED status/Self-
supervision for a faulty hardware module.
2. Inspect the IED visually
Inspect the IED visually to find the physical error causes.
If you can find some obvious physical damage, contact ABB for repair or
replacement actions.
3. Check whether the error is external or internal.
Check that the error is not caused by external origins.
Remove the wiring from the IED and test the input and output operation
with an external test device.
If the problem remains, contact ABB for repair or replacement actions.
7.1.2 Identifying runtime errors
1. Check the error origin from the IED's supervision events Main menu/
Monitoring/IED status/Self-supervision.
2. Reboot the IED and recheck the supervision events to see if the fault has cleared.
3. In case of persistent faults, contact ABB for corrective actions.
7.1.3 Identifying communication errors
Communication errors are normally communication interruptions or synchronization
message errors due to communication link breakdown.
In case of persistent faults originating from IED's internal faults such as
component breakdown, contact ABB for repair or replacement actions.
7.1.3.1 Checking the communication link operation
To verify communication, check that both LEDs above the RJ-45 communication
port are lit.