12.1.7 Technical data
Table 336: ZCPSCH (85) technical data
Function
Range or value Accuracy
Scheme type Disabled
Intertrip
Permissive UR
Permissive OR
Blocking
DeltaBlocking
-
Operate voltage, Delta V (0–100)% of VBase ± 5.0% of ΔV
Operate current, Delta I (0–200)% of IBase ± 5.0% of ΔI
Operate zero sequence voltage,
Delta 3V0
(0–100)% of VBase ± 10.0% of Δ3V0
Operate zero sequence current,
Delta 3I0
(0–200)% of IBase ± 10.0% of Δ3I0
Co-ordination time for blocking
communication scheme
(0.000-60.000) s ± 0.5% ± 10 ms
Minimum duration of a carrier send
signal
(0.000-60.000) s ± 0.5% ± 10 ms
Security timer for loss of guard signal
detection
(0.000-60.000) s ± 0.5% ± 10 ms
Operation mode of unblocking logic Disabled
NoRestart
Restart
-
12.2 Current reversal and WEI logic for distance protection
3-phase ZCRWPSCH (85)
12.2.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and WEI logic for
distance protection 3-phase
ZCRWPSCH - 85
12.2.2 Functionality
The current reversal function is used to prevent unwanted operations due to current
reversal when using permissive overreach or unblock protection or unblocking schemes
in application with parallel lines.