GUID-A25A2575-C368-4FA0-B3A3-A0119F7B4194 V1 EN
Figure 20: Creating a data set in IET600
4. To add a new data set, right-click the area containing the data set names and
select Insert new row the shortcut menu.
5. Define the LN where the data set is to be placed (accept preselected “LD0/
LLN0”) and give the data set a unique name.
GUID-73606F1C-AD21-4DAC-9B35-9D2C94F07410 V1 EN
Figure 21: Naming a data set in IET600
After creating the GOOSE data sets, define the data attributes for the data sets.
If quality data attributes are added to a data set, they must be located
after the status value of the corresponding data object.
1MRS757809 C Section 5
GOOSE
REC615 and RER615 41
Engineering Guide