The received GOOSE data set can contain signals on the data attribute or data object
level. Data object level GOOSE entries can only be received of the following CDC
types: SPS, SPC, ACD, ACT, DPS, DPC, INC, INS, ENC and ENS. Other CDC types
can be connected to application only when dataset is defined in attribute level.
Defining data entries with IET600
1. Select the Datasets tab on the editor pane.
2. Select a GOOSE data set.
3. Using the selection lists below the data set grid, select a data attribute or data
object to be used.
Click Append >> to add the data attribute to the end of the data set.
Click Insert > to add the data attribute above the selected row in the data
set entries list.
A maximum of 80 data attributes can be added in total to the IED's GOOSE data
sets. Recommendation is to divide the attribute amount to 20 per GOOSE data
set for maximum performance in sender/receiver.
GUID-DBE065FB-C0C0-428A-A0A1-53F8D76C4025 V1 EN
Figure 22: Adding data set entries
The possible amount of attributes that can be added to a data set
and the amount of already added attributes are shown above the
data set entries list. However, since IET600 cannot make a
difference between the maximum data attribute count of a data
set for vertical reporting and a GOOSE data set, too high a
maximum value is shown for a GOOSE data set.
Section 5 1MRS757809 C