148 | RMC-100| 2105552MNAE
Figure 7-32: Calibration complete
30. Verify that the Entry, Reading, and Target values update, and the Current Value field displays
the calibrated value based on the defined range (Figure 7-33
). In this example the input signal
from the calibrator is 12 mA. This value represents 750 PSI.