2105552MNAE  |  RMC-100  |  147 
26.  Click 50% Cal Point. The Enter 50% Calibration Value dialog displays with the target mid 
value automatically calculated. For example, 750.000 for the range value of 1500 (
Figure 
7-31). 
27.  Adjust the calibrator to apply the mid-range value (50%) of the signal range. For example, if 
the signal range of the external device is 4 to 20 mA, apply 12 mA. 
28.  Observe the value in the Current Reading field (Figure 7-31
). The displayed voltage value for 
12 mA is approximately 3 Vdc When the value stabilizes, click OK. 
Figure 7-31: Mid (50%) calibration value 
29.  Click OK when the Calibration Complete message displays (Figure 7-32
).