AO895 Section 3 Run-time Operation
112 3BSE027630-600 B
collects information about HART instruments on the channels (HART
command 0 performed).
If new devices are connected to an AO895 module, or if the devices are changed
at specific channels of the module, executing the Perform master reset option
ensures that the devices are detected, see
Connecting a HART instrument on page
147.
Re
ad additional device status
This function will read additional s
tatus for the module. These are:
Operations in progress
Hardware faults
Instruments scan faults and status
Instruments communication error bits
Instruments status bits
See I/O Module Status area for more information.
Flush
completed delayed response
This function will delete the response that is stored
in the buffer. If the DTM is
in a lock situation when the I/O module always response busy then this
function can be used to flush the HART response buffer.
Re
ad gateway parameters
This function will read gateway parame
ters for the module. These are:
Number of instruments in list
Number of instruments scanned
Delayed response, primary master
Scan enabled
Number of retries for busy response
Number of retries for error response