Redundant power A failure
For the CI840 or an optical modem.
Red
undant power B failure
For the CI840 or an optical modem.
CI
840 in position A is primary
CI840 in position A is primary in a redundant pair also set if used as single.
CI
840 in position B is primary
CI840 in position B is primary in a redundant pair.
CI840 err
or on unit in position A
CI840 in position A is erroneous.
CI840 err
or on unit in position B
CI840 in position B is erroneous.
Red
undant cable A failed
The Profibus cable to CI840 in position A is unconnected or broken.
Red
undant cable B failed
The Profibus cable to CI840 in position B is unconnected or broken.
Station address warning
There
is a mismatch between the actual address on the CI840 and the one
configured in the system or if the address is set above 62. The warning will be
cleared when the system is restarted with the right configuration or if the switch on
the CI840 is changed back to the configured address.
Configuration
This control is not available if the unit is used towards AC 800M. The
configuration data is then set via Control Builder Professional.
For configuration of the module, select the “Configuration” menu item. It shows the
user parameters for the FCI e.g. Output Hold Time.