EasyManua.ls Logo

ABB S800 I/O - Page 68

ABB S800 I/O
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AI815/AI845 Section 3 Run-time Operation
68 3BSE027630-600 B
HART Primary Tab
Figure 27. AI845 - Service - HART Primary Tab
The HART Primary Tab is only shown in Engineering mode. Here you select
through which unit HART communication should happen.
The HART Primary unit can be, but does not have to be, identical with the unit
treated as primary by CI840 seen in Service Control in Commissioning mode. If the
HART Primary module fails, HART communication does not switch over
automatically to the other unit. The user must manually do the switchover.

Table of Contents

Other manuals for ABB S800 I/O

Related product manuals