EasyManuals Logo

AC Tech MC1000 series User Manual

AC Tech MC1000 series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
38
NOTE: If TB-13A, TB-13B, and TB-13C are all programmed to select speed
references, and two or three of the terminals are closed to TB-2, the higher terminal
has priority and will override the others. For example, if TB-13A is programmed
to select 0-10VDC, and TB-13C is programmed to select PRESET SPEED #3,
closing both terminals to TB-2 will cause the drive to respond to PRESET SPEED
#3, because TB-13C overrides TB-13A.
14.2.7 ANALOG OUTPUT SIGNALS
There are two terminals that can supply analog output signals proportional to
output frequency or load. Terminal TB-10A can provide a 0-10 VDC or a 2-10
VDC signal proportional to output frequency, and TB-10B can provide the same
signals proportional to load. The 2-10 VDC signals can be converted to a 4-20 mA
signal using a resistor in series with the signal such that the total load resistance is
500 Ohms. See Parameters: 42 - TB10A OUT, 43 - @TB10A, 44 - TB10B OUT,
and 45 - @TB10B in Section 18.0 - DESCRIPTION OF PARAMETERS.
NOTE: These analog output signals cannot be used with “loop-powered” devices
that derive power from a 4-20 mA signal.
14.2.8 DRIVE STATUS OUTPUT CONTACTS
The control board has one Form C relay at terminals TB-16, TB-17, and TB-18.
Contacts are rated 2 amps at 28 VDC or 120 Vac.
There are also two open-collector outputs at terminals TB-14 and TB-15. The
open-collector circuit is a current-sinking type rated at 30 VDC and 40 mA
maximum. An external power supply (30 VDC max) must be used to power the
open-collector outputs. The drive does not have a dedicated power supply for the
open-collector outputs.
The Form C relay and the open collector outputs can be programmed to indicate
any of the following: RUN, FAULT, /FAULT (INVERSE FAULT), LOCK
(FAULT LOCKOUT), AT SPEED, ABOVE #3, I LIMIT (CURRENT LIMIT),
or AUTO/MAN. See Parameters: 52 - TB14 OUT, 53 - TB15 OUT, and 54 -
RELAY. Refer to Section 6.2.5 for a complete description of each of these status
indications.

Other manuals for AC Tech MC1000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the AC Tech MC1000 series and is the answer not in the manual?

AC Tech MC1000 series Specifications

General IconGeneral
BrandAC Tech
ModelMC1000 series
CategoryDC Drives
LanguageEnglish

Related product manuals