Fieldbus Interface
110
Input Array data format – detailed description:
Input Array Word 0, Byte 0 - Actuator and Operating Mode Status
Bit Function Value Status Indicated
7 In Limit
1 The actuator has retracted to the In limit position.
0 The actuator is not at the In limit position.
6 Out Limit
1 The actuator has extended to the Out limit position.
0 The actuator is not at the Out limit position.
5
Servo
Center
1 The actuator has reached the Servo-Center position.
0 The actuator is not at the Servo-Center position.
4 Inhibit
1 The inhibit input is asserted.
0 The inhibit input is not asserted.
3 No Fault
1 The controller is operating correctly. There are no operating faults.
0
The controller is not operating correctly. Refer to page 23 for more
information about fault conditions.
or
An Edge-loss condition has occurred. This option is enabled by setting
parameter 47. Refer to page 19 for more information about setting
controller parameters.
2
CL w/One
Detector
1 The controller is operating in Centerline mode with one detector.
0 The controller is not in Centerline mode with one detector.
1
Fusion
Mode
1 The controller is operating in Fusion mode.
0 The controller is not operating in Fusion mode.
0
Super
Centerline
1 The controller is operating in Super Centerline mode.
0 The controller is not in Super Centerline mode.