EasyManua.ls Logo

Agilent Technologies N5161A - Page 67

Agilent Technologies N5161A
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Agilent N5161A/62A/81A/82A/83A MXG Signal Generators Service Guide
Troubleshooting
The Green Front Panel Power Switch LED or Yellow Standby LED is Not Working
1-59
f. See Figure 1-26. Use a voltmeter with a small probe to measure the output voltage +5.1V on the A6 DC-AC Inverter Interface
assembly at J1-34.
If the voltage is within limits, the fault is likely with the A6 DC-AC Inverter Interface Board. Refer to
“A6 DC-AC Inverter Interface Board (N5181A/82A/83A)” on page 1-34 to troubleshoot.
If the voltage is not within limits, measure J6-34 on the A3 RF assembly. Refer to Figure 1-25.
If the voltage is within limits, replace W1.
If the voltage is not within limits, go to step 4.
Figure 1-26 +5.1V on A6 at J1-34
4. See Figure 1-27. Use a voltmeter with a small probe to measure the output voltage +5.1SB on the A3 RF assembly at J10-F23.
Figure 1-27 +5.1SB at J10-F23
If the voltage is not within limits, the fault is likely with the A1 Power Supply. Replace the A1 Power Supply.
If the voltage is within limits:
J1-34
深圳德标仪器 135-1095-0799

Table of Contents

Other manuals for Agilent Technologies N5161A

Related product manuals