EasiCool™Precision Air Conditioning
System Conguration
Features
Downow Upow
X Type WX Type X Type WX Type
Heating
Electric Heat
Hot gas Reheat
Low Pressure Hot Water
Humidication
Humidier
Hot Water Condensate Pump
Low Conductivity (Soft Water) Bottle
Standard Conductivity (Moderate/Hard Water) Bottle
High Conductivity (Very Hard Water) Bottle
Cleanable Humidier Bottle
Standard Feature Optional Feature Not Available
Heating and Humidication
Heating
Hot Gas Re-Heat (HGRH)
(X Models) Refer to Hot Gas Re-Heat (HGRH).
Or
Electric Heating
Multi-stage nned electric heating elements complete with auto and manual reset overheat cut-out protection.
Electric Heating Thyristor Control
Offers precision control between 0 - 100% via the microprocessor.
Or
Low Pressure Hot Water
A low pressure hot water coil constructed of refrigeration quality copper tube and mechanically bonded aluminium ns
can be factory tted.
Frost protection is tted to prevent freezing of the low pressure hot water coil assembly.
Proportional heating control is provided by a factory tted 3 port, raise/lower type, modulating valve.
Access to the Right hand side of the unit is required to set up the regulating valve