Technical Data Downow Units X Type
Performance Data
Standard Condenser
TC = Total Cooling
SC = Sensible Cooling
(1) All data quoted is gross
Operating Limits
Indoor Air Temperature +18°C to +28°C
Indoor RH% +40% to +55% (based upon 24°C Dry Bulb)
Outdoor Temperature -20°C to +41°C
Cooling Capacity (1) Ambient
Air On 25°C 30°C 35°C 40°C
(DB°C/%RH) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
DF6X-EZRE CR12
22/50 6.5 6.2 6.5 6.2 6.5 6.2 6.1 6.0
24/45 6.8 6.8 6.8 6.8 6.7 6.7 6.4 6.4
26/40 7.1 7.1 7.1 7.1 7.1 7.1 6.8 6.8
DF8X-EZRE CR16
22/50 8.2 8.1 8.2 8.1 8.2 8.1 7.9 7.8
24/45 8.6 8.6 8.6 8.6 8.6 8.6 8.2 8.2
26/40 9.1 9.0 9.1 9.0 9.1 9.0 8.7 8.4
DF10X-EZRE CR16
22/50 10.8 10.7 10.8 10.7 10.6 10.6 10.1 10.1
24/45 11.3 11.3 11.3 11.3 11.1 11.1 10.6 10.6
26/40 11.8 11.8 11.8 11.8 11.6 11.6 11.2 11.2
DF13X-EZRE CR22
22/50 14.0 12.8 14.0 12.8 13.8 12.7 13.1 12.2
24/45 14.6 14.1 14.6 14.1 14.3 13.9 13.6 13.4
26/40 15.1 15.1 15.1 15.1 14.8 14.8 14.1 14.1
DF15X-EZRE CR22
22/50 15.9 14.9 15.9 14.9 15.5 14.7 14.7 14.2
24/45 16.5 16.2 16.5 16.2 16.1 15.8 15.3 15.3
26/40 17.1 17.1 17.1 17.1 16.7 16.7 16.0 16.0
DF17X-EZRE CR30
22/50 18.3 17.0 18.3 17.0 18.0 16.9 17.0 16.2
24/45 18.9 18.6 18.9 18.6 18.5 18.3 17.6 17.5
26/40 19.5 19.5 19.5 19.5 19.1 19.1 18.1 18.1
DF20X2-EZRE CR30
22/50 22.0 20.5 22.0 20.5 21.3 20.0 20.1 19.2
24/45 22.9 22.5 22.9 22.5 22.1 21.9 21.0 21.0
26/40 23.8 23.8 23.8 23.8 23.0 23.0 21.9 21.9
DF22X2-EZRE CR50
22/50 22.6 21.8 22.6 21.8 22.6 21.8 21.7 21.2
24/45 23.6 23.6 23.6 23.6 23.6 23.6 22.7 22.7
26/40 24.7 24.7 24.7 24.7 24.7 24.7 23.7 23.7
DF26X2-EZRE CR50
22/50 27.3 24.9 27.3 24.9 27.3 24.9 25.8 24.0
24/45 28.3 27.3 28.3 27.3 28.2 27.2 26.8 26.2
26/40 29.4 29.4 29.4 29.4 29.3 29.3 27.8 27.8
DF28X-EZRE CR50
22/50 25.7 25.1 25.7 25.1 25.7 25.1 24.5 24.1
24/45 26.9 26.9 26.9 26.9 26.9 26.9 25.6 25.6
26/40 28.2 28.2 28.2 28.2 28.1 28.1 27.0 27.0