Alcatel-Lucent 9130 BSC Evolution - Rear RITs and Fillers Replacement

Alcatel-Lucent 9130 BSC Evolution
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Maintain the ATCA Subrack
3.6 Rear RITs
This section covers the replacement of the following ATCA Subrack Rear RITs:
JAXPC: Personality Card
JAXSSW: Rear Transition Module
JAXSMM : Shelf Management Controller
JBXPS: Power Entry Modules
A large number of cables run at the rear of the BSC. While working on a RIT,
ensure you do not accidentally disconnect cables from other RITs.
3.6.1 Replace JAXPC
Help: The two JAXPC boards slots, located on the right side of the JAXSMMs,
are numbered from 1 on the right to 2 on the left, on the back side of each
side of the subrack chassis.
The SBL number for the JAXPC1 (from the right side - logical slot 49) is 2,
while the SBL number of the JAXPC2 (from the left side - logical slot 50) is 3,
therefore the alarms for the unplugged boards will be displayed at BSC terminal
for the BSC-ENV SBL with number 2 or 3.
The following figure shows the front view for JAXPC board.
Open
Closed
OOS
OK
Handle
H/S
Alarm/
Reset
Telco Alarms & Relays
Failure LED
Power LED
Hot Swap LED
Alarm Reset Push Button
Alarm I/O Connector
Figure 16: JAXPC Board Front View
3BK 21281 AAAA PCZZA Ed.13 47 / 90