84 Rockwell Automation Publication 1444-UM001D-EN-P - June 2018
Chapter 2 Install the Dynamix 1444 Series Monitoring System
Proximity Probes
The connected channel of the Tachometer Signal Conditioner must be
configured with:
• Transducer Type = Eddy Current Probe System, and
• Transducer Power = -24V DC
Wire the eddy current probe as illustrated.
Figure 32 - Channel 0 Wiring for an Eddy Current Probe Sensor
* Shield can be landed to any available shield connection. See the IMPORTANT note on page 56 for additional information.
Figure 33 - Channel 1 Wiring for an Eddy Current Probe Sensor
* Shield can be landed to any available shield connection. See the IMPORTANT note on page 56 for additional information.
Shield Floating
Common
Signal
Shield
-24V DC
3
1
2
1
7
23
7*
1
6
712
24 19
18 13
Shield Floating
Common
Signal
Shield
-24V DC
6
4
5
10*
24
19
18 13
1
6
7
12
4
10
56