Equipment Phase Instructions
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018 441
PXRQ Error Codes
ERR (hex) EXERR (hex) Description Recommended Action
00 0000 The PXRQ instruction was aborted
before it sent the request to
FactoryTalk Batch software.
None
01 0000 The PXRQ instruction was aborted
after it sent the request to FactoryTalk
Batch software
None
02 0000 Two or more PXRQ instructions
executed at the same time using the
same request type
Limit execution to one PXRQ instruction at a time.
03 0110 Communication error. The request
was not delivered because there is no
subscriber to the phase
Check that FactoryTalk Batch software is connected and
running.
0210 Communication error. The request
was not delivered because there is no
connection to the Notify object.
0410 Communication error. Delivery failed.
1010 Communication error. The request
was not delivered because FactoryTalk
Batch software does not subscribe to
receive the external request.
1020 FactoryTalk Batch software is not
attached to the phase.
04 0002 The FactoryTalk Batch software
encountered an error while processing
the request.
Check the connection and communication path to
FactoryTalk Batch software.
0003 The PXRQ instruction contains an
invalid value.
0004 FactoryTalk Batch software is not in
the proper state to process the
request.
0005 Two or more PXRQ instructions
executed at the same time using
different request types
0006 Error storing to parameter tags at end
of request processing.
05 0000 FactoryTalk Batch software received
the request but passed back an invalid
cookie.
Check the connection and communication path to
FactoryTalk Batch software.
06 0000 PXRQ instruction sent an invalid
parameter to FactoryTalk Batch
software.
Check the connection and communication path to
FactoryTalk Batch software.
07 0000 Communication lost while PXRQ is
waiting for response from the external
sequencer.
Check the connection and communication path to
FactoryTalk Batch software.
Affects Math Status Flags
No