Page #477 background image
Equipment Sequence
Chapter 8
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018 477
SOVR instruction ran successfully. The other four codes indicate that the
instruction did not run successfully and provide additional information about the
reason for the instruction failure.
Available Languages
Ladder Diagram
Function Block
This instruction is not available in Function Block.
Structured Text
SOVR(SequenceName,Command,Result)
Operands
The SOVR instruction uses the following operands.
Operand Type Format Description
Sequence Name Sequence Name of the Equipment
Sequence
Equipment Sequence to change to a different state. For
example, Make_Product_101.
Command Command Name of the command Command to send to the Equipment Sequence and change
state. Use one of these commands:
• HOLD
• STOP
• ABORT
Result DINT Immediate tag For an instruction to return a success or failure code, enter a
DINT tag where the result code is stored. Otherwise, enter 0.
Affects Math Status Flags
No.
Major/Minor Faults
The SOVR instruction cannot trigger a fault, so there are no fault conditions for
this instruction.

Table of Contents

Other manuals for Allen-Bradley LOGIX 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley LOGIX 5000 and is the answer not in the manual?

Allen-Bradley LOGIX 5000 Specifications

General IconGeneral
BrandAllen-Bradley
ModelLOGIX 5000
CategoryController
LanguageEnglish

Related product manuals