3-4 Programming and Parameters
Basic Display Group (continued)
b006 [Drive Status] Related Parameter(s): A095
Present operating condition of the drive.
Values Default: Read Only
Min/Max: 0/1
Display: 1
1 = Condition True, 0 = Condition False
Running Bit 0
Forward Bit 1
Accelerating Bit 2
Decelerating Bit 3
b007 [Fault 1 Code]
b008 [Fault 2 Code]
b009 [Fault 3 Code]
A code that represents a drive fault. The codes will appear in these parameters in the order they occur
(b007
[Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once.
Refer to Chapter
4 for fault code descriptions.
Values Default: Read Only
Min/Max: F2/F122
Display: F1
b010 [Process Display] Related Parameter(s): b001, A099
32 bit parameter.
The output frequency scaled by A099
[Process Factor].
Values Default: Read Only
Min/Max: 0.00/9999
Display: 0.01 – 1
32
Output
Freq
Process
Factor
Process
Display
=
x

Table of Contents

Other manuals for Allen-Bradley PowerFlex 40P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 40P and is the answer not in the manual?

Allen-Bradley PowerFlex 40P Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 40P
CategoryController
LanguageEnglish

Related product manuals