EasyManua.ls Logo

Allen-Bradley PowerFlex 755T - Page 129

Allen-Bradley PowerFlex 755T
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 750-IN100B-EN-P - July 2017 129
Power Wiring Chapter 5
Table 14 - PowerFlex 755TM Common Bus Inverter Jumpers
Supply Source
Type
Grounding Scheme EMC
Option
PE-A PE-A1 PE-A2 PE-B1
(MOV on the AC
Precharge
Control Circuit
Board)
(MOV in the TVSS
Module)
(Common Mode
Caps on All AC
Common Mode
Filter Circuit
Boards)
(Y-Caps on Line
Side Converter
Power Interface
Circuit Boards)
(Y-Caps on Motor
Side Inverter
Power Interface
Circuit Boards)
Regenerative Factory Default C3 N/A N/A N/A N/A Disconnected (Out)
Grounded C2
(2)
N/A N/A N/A N/A TBD
C3 N/A N/A N/A N/A Disconnected (Out)
Ungrounded/High-
resistance Ground
(1)
N/A N/A N/A N/A N/A Disconnected (Out)
Marine Ungrounded /
High Resistance
Ground
(1)
N/A N/A N/A N/A N/A TBD
Non-Regenerative
(third-party)
Factory Default C3 N/A N/A N/A N/A Disconnected (Out)
Grounded C2
(2)
N/A N/A N/A N/A TBD
C3 N/A N/A N/A N/A Disconnected (Out)
Ungrounded/High-
resistance Ground
(1)
N/A N/A N/A N/A N/A Disconnected (Out)
Marine Ungrounded /
High Resistance
Ground
(1)
N/A N/A N/A N/A N/A TBD
(1) Ungrounded and high-resistance ground systems do not meet the EMC Directive due to the disconnected jumper positions.
(2) Full compliance requires an optional EMC solution that is mounted in a dedicated enclosure. Rockwell Automation is evaluating the ability to meet Category C2 compliance. Contact the factory for
more information.