Value Description
41 55 Pound Tumble Dryer
42 75 Pound Tumble Dryer
43 120 Pound Tumble Dryer
44 170 Pound Tumble Dryer
45 200 Pound Tumble Dryer
46 F75 Pound Tumble Dryer
Table 14
Machine Config Test #4
This option shows which dipswitches are set on the control.
To enter, press the or keypads in the Individual Diagnostic
Tests Menu until Machine Config Test #4 is highlighted and then
press the keypad. The display will show "XXX", with "XXX"
representing the machine capacity. Refer to Table 15 .
ConfigValue Heat Type
120VAC Sup-
ply
0 Non-IEC Gas YES
1 Non-IEC Gas NO
64 Electric YES
65 Electric NO
128 IEC Gas YES
129 IEC Gas NO
192 Steam YES
193 Steam NO
Table 15
If supply voltage is 100-127VAC per phase, the voltage configu-
ration should be 120VAC.
If supply voltage is 200-240VAC per phase, the voltage configu-
ration should be 240VAC.
To exit test, press the
keypad. keypad will exit all tests.
Machine Config Test #5
This option shows the machine configuration values for the volt-
age.
To enter, press the or keypads in the Individual Diagnostic
Tests Menu until Machine Config Test #5 is highlighted and then
press the
keypad. The display will show "XXX", with "XXX"
representing the configuration value. Refer to Table 16 .
Config Value
Adjust Fan
Speed for
Heat Type
480V Motor
Drives (1 for
Yes, 0 for No)
2 Gas/Steam 0
3 Gas/Steam 1
4 Electric 0
5 Electric 1
6 Eco Gas 0
7 Eco Gas 1
8 Eco Electric 0
9 Eco Electric 1
10 Low kW Electric 0
11 Low kW Electric 1
Table 16
To exit test, press the keypad. keypad will exit all tests.
ICM Alarm Status (gas models only)
This option shows the status of the ICM (Ignition Control Mod-
ule) Alarm.
To enter, press the or keypads in the Individual Diagnostic
Tests Menu until ICM Alarm Status is highlighted and then press
the
keypad. The display will show "Locked" or "Ready".
To exit the test, press the
keypad. keypad will exit all tests.
Heat Interlock Test
While this test is running, the control will show the status of the
following inputs for two seconds each. The control will continue
scrolling through the input status displays until the test is aborted.
To enter, press the or keypads in the Individual Diagnostic
Tests Menu until Heat Interlock Test is highlighted and then press
the keypad. Refer to sections below for more details on indi-
vidual statuses.
NOTE: These switches are tested in sequence. If one
switch is sensed open, the rest will be open as well.
To exit the test, press the keypad. keypad will exit all tests.
Air Flow Switch
The display will show "Air Flow Switch Open" if sensed open for
at least 1.0 seconds or "Air Flow Switch Closed" if sensed closed
for at least 1.0 seconds.