DE-3000 IOI 7-17
All rights reserved © ALTRONIC, LLC 2017
42
The alarm may be acknowledged by pressing the F2 key as shown:
STATUS RUNNING
ALARMED (ACK)
CHAN 12 26.3 PSIG
MANIFOLD AIR PRESS
RUNNING
PRESS TO
ACKNOWLEDGE
ALARM
F2
Acknowleding all the alarms will turn off output #6 (typically a horn or light).
Once the alarm is no longer violated, whether its been acknowledged or not, the
2nd line resumes displaying ARMED.
21.0 INTEGRATED TIMER OUTPUTS
21.1 On 2014 and later versions of the DE-3000, digital outputs #5 and #13 may
be configured in the terminal program to be used as integrated timers. When
configured for this function, the digital outputs turn ON at the engine start and
remain ON until a specified amount of time has passed since a stop or fault.
This may be used, for example, to shut down the power to a panel in order to
lengthen battery life. The operation of the integrated timer output is depicted in
the following diagram:
ENGINE
START
STOP/
FAULT
ON
OFF
INTEGRATED OUTPUT TIMER
INTEGRATED
TIMER OUTPUT
DELAY
22.0
TROUBLESHOOTING
22.1 The power LED’s on the Power Supply and Terminal Module are blank as well as
the LCD on the display module:
•
Check the power supply voltage at the 12-24Vdc input terminals; should be
between 12 and 24Vdc.
•
Check the power supply power fuse and replace if blown.
•
If the Terminal Module power LED or the Display Module LCD is not on, make
sure the 25-pin connectors and cable assembly are connected and secured.
STATUS TIMERS ACTIVE
ALARMED (ACK)
CHAN 12 26.3 PSIG
MANIFOLD AIR PRESS
NOTE: A SPARE FUSE (PART NUMBER
601653 - 6.3 AMP) IS PROVIDED ON
THE POWER SUPPLY BOARD.