FIG. 1 AUTOSTART SEQUENCE OF OPERATION
SYSTEM
STATE
0
ENGINE
STOPPED
1
DELAY BEFORE
CRANKING
2
CRANKING
3
PURGE 1
4
PURGE 2
5
STARTING
6
STARTED
7
WARM UP
8
RUNNING
BEGINS ON EVENT
SHOWN TO RIGHT
ON A STOP
OR A FAULT
AUTO
START
SIGNAL
AFTER
TIMER T1
SECONDS
CRANKING CRANKING
AFTER
TIMER T4
SECONDS
ENGINE
FIRING
ENGINE
RUNNING AT
IDLE RPM
ENGINE
RUNNING AT
USER SETTING
ENDS
AUTO
START
SIGNAL
AFTER
TIMER T1
SECONDS
AS
CRANKING
BEGINS
AFTER
TIMER T3
SECONDS
AFTER
TIMER T4
SECONDS
AFTER
TIMER T4
SECONDS
+ FIRING
CRANKING,
MOTOR OFF AT
USER SET RPM
AFTER
WARM UP
TIMER T5
MINUTES
ON A STOP
OR A FAULT
OUT 1
FUEL VALVE
CONDITION OR
STATUS
OFF OFF OFF OFF OFF ON ON ON ON
OUT 2
IGNITION
CONTROL
CONDITION
OR STATUS
OFF OFF OFF OFF ON ON ON ON ON
OUT 3
CRANKING
MOTOR
CONDITION
OR STATUS
OFF OFF ON ON ON ON ON
OFF
LOCKED OUT
OFF
LOCKED OUT
OUT 4
LUBE PUMP
CONDITION
OR STATUS
ON,
THEN OFF
AFTER
POST LUBE
ON FOR
TIMER T2
SECONDS,
THEN OFF
ON FOR
TIMER T2
SECONDS, THEN
OFF
ON FOR
TIMER T2
SECONDS, THEN
OFF
ON FOR
TIMER T2
SECONDS, THEN
OFF
ON FOR
TIMER T2
SECONDS, THEN
OFF
ON FOR
TIMER T2
SECONDS OR
USER OFF RPM
OFF OFF
ANALOG OUT
AO1 VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
PID PER
CONTROL SCHEME
ANALOG OUT
AO2 VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
USER
DEFAULT VALUE
PID PER
CONTROL SCHEME
CLASS A ARMED ARMED ARMED ARMED ARMED ARMED ARMED ARMED ARMED
CLASS B DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED ARMED* ARMED
CLASS C DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED DISABLED ARMED** ARMED
INPUT
SETPOINTS
AND FAULT
SENSOR
FUNCTION
FIRST OUT
FAULT
LOCKED ON
TIMERS NOT
RUNNING
TIMERS
NOT
RUNNING
TIMERS
NOT
RUNNING
TIMERS
NOT
RUNNING
TIMERS
NOT
RUNNING
TIMERS
NOT
RUNNING
B AND C
TIMERS
BEGIN
RUNNING
* B TIMER
DELAYS
** AS CLEARED
OR “C” TIMER
MET
NOTE: AUXILIARY FUNCTIONS force and inhibit as assigned, and auxiliary outputs 3 through 7 are always active